Transformer Fault Current Ranges

This calculation assumes an infinite bus, and the values provided are calculated at the secondary terminals of the transformer. For additional fault information, please contact systemplanning@coserv.com.

Note: CoServ reserves the right to make system modifications including feed changes and transformer upgrades to maintain service without customer notification. System modifications can result in higher fault currents.

Service

Single-phase

Single-phase, 120/240 V
kVA ratingMinimum available fault (A)Maximum available fault (A)
101,0422,778
151,5634,167
252,6046,944
37.53,90610,417
505,20813,889
757,81320,833
10010,41727,778
16717,18134,792
25016,85552,083

Single-phase

Single-phase, 240/480 V
kVA ratingMinimum available fault (A)Maximum available fault (A)
105211,389
157812,083
251,3023,472
37.51,9535,208
502,6046,944
753,90610,417
1005,20813,889
1678,59117,396
2508,42826,042

Three-phase

Three-phase, 120/208 V
kVA ratingMinimum available fault (A)Maximum available fault (A)
753,6217,710
112.55,43110,073
1507,24113,431
22510,86220,146
30014,48226,862
50024,13731,905
75033,86839,131

Three-phase

Three-phase, 277/480 V
kVA ratingMinimum available fault (A)Maximum available fault (A)
751,5693,341
112.52,3534,365
1503,1385,820
2254,7078,730
3006,27611,640
50010,45913,825
75014,59716,957
1,00019,46322,609
1,50029,19433,914
2,00038,92645,219
2,50048,65756,523

No 120/208 V values are listed above 750 kVA.